Technical Data Sheet

Gas to be detected Chlorine gas
Range / Resolution 0 to 20 PPM
Accuracy ±1% of the full scale value.
Sensor type Long life Electrochemical sensor, Imported make
Sensor life Expected 2 year for Electrochemical sensor.
Set point Two independent set point, LO & HI with blinking indication with programmable latch/non-latch facility only for indication purpose. (There is no relay output)
Display Easy- to-read 0.5”, 3.5 digit LCD Display
Setting Setting by 4 keys on front panel i.e. ‘SET / NEXT’, ‘UP’, ‘DOWN’ & ‘TEST / BACK’ keys.
Loop output 4-20mA, with permissible load 750 ohm at 24Vdc, 25mA.
Monitoring i) By display : Shows “Err” indication. Sensor Open/Over Indication
ii) By loop current : Selectable, upscale current : 22mA, Down scale current : 3.6mA to 3.8mA.
Supply Voltage 14VDC to 36VDC, normally 24 VDC, 25mA
Digital filter Select damping factor 1 to 99 to smooth input signal.
Operating ambient Temperature 0 to 50 degree C ± 5%
Relative humidity Below 95%, non condensing.
Sensor Housing P.V.C.
Enclosure Detail FLAMEPROOF , Cast Alluminium alloy, LM-6 / C.I Enclosure, IP-65, As per IS : 2148 – 1981, 145mm (Dia) X 130mm (Height) X 85mm (D) Mounting : Wall Mounting / Stand Mounting, 250 Grams
Model TOX-107-FLP