Loss of Vacuum and High Vacuum switches, for use with Chlorine gas under vacuum. For monitoring of the systems vacuum condition.
Loss of Vacuum Switch
Loss of Vacuum: switch is designed to provide one normally open and one Normally closed alarm contact in the presence of a loss of vacuum. It should be mounted Vertically as close to the Ejector as practical and -after the gas rate valve. The alarm point is adjustable between 28 and 29 Inches of Mercury to allow the switch to actuate at the Required vacuum.
Contacts rated at | 5 A @ 250 Vac or 28 Vdc maximum, (Resistive Load), |
Enclosure | NEMA 4X. |
Dimensions | 102 mm W x 94 mm D x 145 mm H. |
Weight | 2 kg. |
High Vacuum Switch
BM5987, High Vacuum switch is designed to provide one normally open and one normally closed alarm contact in the presence of a high vacuum level. It should be mounted Vertically as close to the Vacuum Regulator as practical and before the gas rate valve. The alarm point is adjustable between 2 and s: Inches of Mercury to allow the switch to actuate at the required vacuum.
Contacts rated at | 5 A @ 250 Vac or 28 Vdc maximum, (Resistive Load) |
Enclosure | NEMA 4X. |
Dimensions | 102 mm W x 94 mm D x 145 mm H. |
Weight | 2 kg. |
ITEM | QTY | Description |
---|---|---|
1 | 1 | ADJUSTMENT PLUG |
2 | 1 | O-RING |
3 | 1 | HOUSING BCDY |
4 | 1 | SPRING |
5 | 2 | SCREW, 6-32 X 3/8 LG BD HD |
6 | 1 | SPRING ADAPTOR |
7 | 1 | LOWER DIAPHRAGM PIN |
8 | 2 | DIAPHRAGM |
9 | 1 | DIAPHRAGM SPACER |
10 | 1 | UPPER DIAPHRAGM PIN |
11 | 1 | DIAPHRAGM SEAL |
12 | 1 | ENCLOSURE |
13 | 2 | SCREW, 10-24 X 3/8 LG RD HD |
14 | 2 | SCREW, 2 -56 X 1/2 LG RD HD |
15 | 1 | MICROSWITCH |
16 | 1 | LEVER ASSEMBLY |
17 | 2 | NUT, 10-24 |
18 | 2 | SCREW, 10- 24 X 1/2 LG RD HD |
19 | 1 | MOUNTING BRACKET |
20 | 1 | TUBING CONNECTOR, 1/4 X 3/8 X 90' |
21 | 1 | SCREW, 2-56 X 3/16 LG RD HD |
Item | Part Number | |
---|---|---|
Low Vacuum | High Vacuum | |
4 | R-5589 | R-5588 |